Item |
Model |
XG1K/1KL |
XG2K/2KL |
XG3K/3KL |
Capacity |
VA / Watts |
1KVA / 0.8KW or 0.9KW |
2KVA / 1.6KW or 1.8KW |
3KVA / 2.4KW or 2.7KW |
input |
Normal voltage |
220VAC or 110VAC |
Turn on Voltage range |
(115+-5~300+-5)VAC or ( 60+-5-138+-5)VAC |
Frequency range |
40~60Hz(adjustable) |
40~60Hz(adjustable) |
40~60Hz(adjustable) |
Input power factor |
>0.99(220VAC,full R load) |
Generator |
Support generator input(Generator rating≥2*UPS rating ) |
line low loss/comeback |
220VAC:(110±5)VAC/(195±5)VAC when Load≤55%, 110VAC:(60±3)VAC/(65±3)VAC when load≤40% |
220VAC:(130±5)VAC/(195±5)VAC when56%< Load≤65%, 110VAC:(60±3)VAC/(75±3)VAC when40%< load≤50% |
220VAC:(150±5)VAC/(195±5)VAC when66%< Load≤70%, 110VAC:(70±3)VAC/(75±3)VAC when50%< load≤60% |
220VAC:(160±5)VAC/(195±5)VAC when71%< Load≤90%, 110VAC:(70±3)VAC/(85±3)VAC when60%< load≤70% |
220VAC:(185±5)VAC/(195±5)VAC when Load>90%, 110VAC:(90±3)VAC/(95±3)VAC when load>70% |
Output |
Voltage range |
200VAC/208VAC/220VAC/230VAC/240VAC/110VAC/120VAC, need confirm before order |
Frequency range |
50Hz or 60HZ+-0.2Hz(Battery mode) |
Wave form |
Pure Sine Wave |
Transfer time |
0 ms, Between Line mode and Bat mode |
Transfer time: 4ms (typical 2.5ms), line Mode and bypass mode |
Distortion |
≤4%,Full linear load |
≤4%,Full linear load |
≤4%,Full linear load |
Degree of distortion |
≤7%,Full nonlinear load |
≤7%,Full nonlinear load |
≤7%,Full nonlinear load |
Overload capacity |
<105% warning only, <125% 30s ; <150% 20s,>150%, 300MS to bypass |
Load peak ratio |
3:1(max) |
Standard Modes XG1-3K |
Battery Type |
Maintenance free valve regulated lead acid (VRLA) battery |
Battery voltage |
24VDC or 36VDC |
48VDC or 72VDC |
72VDC or 96VDC |
Internal Battery |
2*7AH(9AH) or 3*7AH |
4*7AH(9AH) or 6*7AH or 8*7AH |
6*7AH(9AH) or 8*7AH |
Recharge time |
5 hours to 90%capacity |
Charge Current |
1A |
1A |
1A |
Long backup ModeXG1-3KL |
Battery bank |
36VDC, External |
72VDC,External |
96VDC,External |
Charge Current |
5Amp,Max 7Amp |
5Amp,Max 7Amp |
5Amp,Max 7Amp |
Display |
LED Mode |
Load level / Battery level / Battery mode / Line mode / Inverter , Bypass ,Over load , Fault |
LCD Mode |
input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp.LCD For input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp. LED for line,bat, Inverter, Bypss |
Audible Alarm |
Battery Mode |
Beeping every 4 seconds (re-settable) and every second when battery low |
Overload |
Beeping twice every second |
Fault |
Beeping Continuously |
Bettery low/charger fault |
Beeping every 1 second |
Bypass mode |
Beeping every 2 min |
L/N inverse |
Beeping every 2 min |
Communications |
RS-232/USB Interface |
With monitoring software |
Working Environment |
Surge protection |
RJ-45 I/O port available for network or Fax/Modem |
Working temperature |
- 20ºC~40ºC |
Humidity |
0-95% non-condensing |
Product size |
WxDxH (mm) |
350*145*230(H) |
430*190*328(H) |
430*190*328(H) |
PCS/CTN |
|
2 |
1 |
1 |
CTN size |
WxDxH (mm) |
495*470*340(H) |
570*305*450 (H) |
570*305*450 (H) |
N/W, CTN XG1-3K |
Kg |
19/23 (base on 7AH) |
19/23/28 (base on 7AH) |
24/28 (base on 7AH) |
N/W, CTN XG1-3KL |
|
12 |
12 |
12 |
G/W, CTN XG1-3K |
Kg |
21/25 |
21/25/30 |
25/30 |
G/W, CTN XG1-3KL |
|
15 |
14 |
14 |
REMARK |
XG*K --- Standard Type Internal battery, XG*KL Long Time Type,External battery |