| Customization: | Available |
|---|---|
| Phase: | Single Phase |
| Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Model | NTA 2K(B) | NTA 3K(B) | NTA 6K(B) | NTA 10K(B) | NTA 15K | NTA 20K | |
| Input | Rated Voltage | 220VAC or 110V | |||||
| Phase | L+N+G | ||||||
| Voltage Range | 220 or 110±25% VAC | ||||||
| Rated Frequency | 50Hz or 60HZ | ||||||
| Frequency Range | 40-60HZ, default:46~54Hz, adjustable by softwave | ||||||
| Power Factor | Max 0.8 | ||||||
| Generator | Support generator input, 2*UPS rating | ||||||
| Output | VA/Watt | 2KVA/1.6kW | 3KVA/2.4KW | 6KVA/4.8KW | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW |
| Rated Voltage | 220 or 110VAC ±2% | ||||||
| Phase | L+N+G | ||||||
| Voltage Range | 200/208/220/230/240VAC, Could be adjusted by software. 10% derating for 208VAC/200VAC | ||||||
| Bypass output before turn-on | Yes | ||||||
| Crest Ratio | 3:1 | ||||||
| Frequency | 50Hz | ||||||
| Efficiency Line Mode | > 80% (R Load) | > 87% (R Load) | |||||
| Efficiency Battery Mode | > 85% (R Load) | > 88% (R Load) | |||||
| Overload | Line Mode/Battery Mode | Overload warning only | |||||
| 2Min,then transfer to bypass and alarm. | |||||||
| 30S,then transfer to bypass and alarm. | |||||||
| 0.5S,then transfer to bypass and alarm. | |||||||
| Automatically Recovery | Yes | ||||||
| Short circuit protection | Line/Battery Mode | Cut off output and alarm after 3S | |||||
| Transfer time | Line to Battery Mode | 0ms, Line/battery mode | |||||
| Battery | Rated Voltage | 192VDC | |||||
| Standard Mode | 16*7AH | 16*7AH | 16*7AH(9AH) | 16*7AH(9AH) | .N/A | .N/A | |
| Protection | Low Alarm Voltage/ Comeback Voltage |
(180.8V±4V)/ (188.8V±4V) | |||||
| Shutdown Voltage | (176V±4V)/ (184V±4V) | ||||||
| (160V±4V)/ (168V±4V) | |||||||
| Battery protection | Overcharge Protection | (250V±4V) | |||||
| Battery Self Test | Support, Weak and Fault | ||||||
| Charger | Output Voltage | (220±2)VDC, Floating Charge | |||||
| Charge Time | Determined by battery capacity | ||||||
| Charging Current | 1.5A/5A | 1.5A/5A | 7A | 7A | 7A | 7A | |
| Interface | Alarm Silence | Support | |||||
| DC Power Turn-on | Support | ||||||
| Automatic Restart | Support | ||||||
| Alarm | Battery Mode | Beep/4s | |||||
| Battery Low/Charger Fault | Beep/1s | ||||||
| UPS Fault | Beeping Continuously | ||||||
| Overload | Beep/1s | ||||||
| Bypass Mode | Beep/2Min | ||||||
| Communication | RS232/RS485 with Monitor softwave ,Intelligent slot, SNMP Optoion | ||||||
| Cooling | Forced Air Cooling | Yes | |||||
| Display | LED and LCD | input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp.LCD For input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp. LED for line,bat, Inverter, Bypss | |||||
| Environment | Working Temperature | 0ºC~40ºC | |||||
| Altitude | <1000m | ||||||
| Audible Noise | ≤55dB | ||||||
| Storage Temperature | -15ºC~45ºC | ||||||
| Working Humidity | 20%~95% | ||||||
| product size | L*W*H(mm) | 560*260*717mm | 900*370*655 | ||||
| package size | L*W*H(mm) | 710*990*440mm | 1054*450*730 | ||||
| N.W. | N.W.(Kg) | 85(16*9AH)/37 | 89(16*7AH)/40 | 58 | 62 | 155 | 160 |
| G.W. | Weight(Kg) | 101(16*7AH)/42 | 105(16*7AH)/45 | 76 | 80 | 170 | 175 |