Item | Model | XG6K-TXB | XG6KS-TX | XG10K-TXB | XG10KS-TX |
Capacity | VA / Watts | 6KVA/5.4KW | 6KVA/4.8KW | 10KVA/9KW | 10KVA/8KW |
Input | Normal Voltage | L+N+G=220VAC or L1 110+L2 110=220V | |||
Turn On Voltage Range | (120±5~274±5)VAC | ||||
Frequency Range | 40~60Hz±0.2(adjustable) | ||||
Input Power Factor | >0.99(220VAC,full R load) | ||||
Generator | Support generator input(Generator rating≥2*UPS rating ) | ||||
Line Low Loss/Comeback | 220VAC:(120±5)VAC/(140±5)VAC when Load≤50% | ||||
220VAC:(150±5)VAC/(165±5)VAC when 50%< Load≤80% | |||||
220VAC:(160±5)VAC/(180±5)VAC when 80%< Load≤90% | |||||
220VAC:(175±5)VAC/(190±5)VAC when Load>90% | |||||
Output | Voltage Range | 200VAC/208VAC/220VAC/230VAC/240VAC, need to confirm before order(Could be adjusted by software,10% derating for 208VAC/200VAC) | |||
Frequency Range | 40~60Hz±0.2(adjustable) | ||||
Wave Form | Pure Sine Wave | ||||
Transfer Time | 0 ms, Between Line mode and Bat mode | ||||
Transfer time: 4ms (typical 2.5ms), line Mode and bypass mode | |||||
Voltage Distortion | ≤6%,Full RCD load | ||||
Voltage Distortion | ≤2%,Full R load | ||||
Overload Capacity | load≤105%±5%, warning only, 105%+-5%<Load≤125% +-5% ,1min ; 125%±5%<load≤135%±5% , 30S ; Load>135%±5%, 100MS | ||||
Load Peak Ratio | 3:1(max) | ||||
Battery | Battery Type | Maintenance free valve regulated lead acid (VRLA) battery | |||
Battery Voltage | 192VDC | ||||
Battery Capacity | 16*7AH | External | 16*9AH | External | |
Recharge Time | 7 hours to 90% capacity | Depended on battery capacity |
7 hours to 90% capacity | Depended on battery capacity |
|
Charge Current | 1A | Normal 5Amp. Max 7Amp | 1A | Normal 5Amp. Max 7Amp | |
Display | LED Mode | Load level / Battery level / Battery mode / Line mode / Inverter , Bypass ,Over load , Fault | |||
LCD Mode | LCD For input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp. Fault Code ,LED for line,bat, Inverter, Bypss,Fault | ||||
Audible Alarm | Battery Mode | Beeping every 4 seconds (re-settable) | |||
Overload | Beeping every 1 min | ||||
Fault | Beeping Continuously | ||||
Bettery Low/Charger Fault | Beeping every 1 min | ||||
Bypass Mode | Beeping every 2 min | ||||
L/N Inverse | Beeping every 2 min | ||||
Communications | RS-232/USB Interface | With monitoring software | |||
Working Environment | Surge protection | RJ-45 I/O port available for network or Fax/Modem | |||
Working Temperature | 0ºC~40ºC | ||||
Humidity | 0-95% non-condensing | ||||
Product size | WxDxH (mm) | 540*260*720 | 260*533*560 | 540*260*720 | 260*533*560 |
Product Weight | Kg | 85 | 53 | 93 | 55 |
PCS/CTN | 1 | 1 | 1 | 1 | |
CTN size | WxDxH (mm) | 730*440*1000 | 360*640*760 | 730*440*1000 | 360*640*760 |
CTN Weight(G/W) | Kg | 94 | 62 | 102 | 64 |
REMARK | XG*K-TXB --- Standard Type Internal battery with Transformer, XG*KS-TX---- Long backup Type With Transformer,External battery |