Item |
Model |
XG6K-TXB |
XG6KS-TX |
XG10K-TXB |
XG10KS-TX |
Capacity |
VA / Watts |
6KVA/5.4KW |
6KVA/4.8KW |
10KVA/9KW |
10KVA/8KW |
Input |
Normal Voltage |
L+N+G=220VAC or L1 110+L2 110=220V |
Turn On Voltage Range |
(120±5~274±5)VAC |
Frequency Range |
40~60Hz±0.2(adjustable) |
Input Power Factor |
>0.99(220VAC,full R load) |
Generator |
Support generator input(Generator rating≥2*UPS rating ) |
Line Low Loss/Comeback |
220VAC:(120±5)VAC/(140±5)VAC when Load≤50% |
220VAC:(150±5)VAC/(165±5)VAC when 50%< Load≤80% |
220VAC:(160±5)VAC/(180±5)VAC when 80%< Load≤90% |
220VAC:(175±5)VAC/(190±5)VAC when Load>90% |
Output |
Voltage Range |
200VAC/208VAC/220VAC/230VAC/240VAC, need to confirm before order(Could be adjusted by software,10% derating for 208VAC/200VAC) |
Frequency Range |
40~60Hz±0.2(adjustable) |
Wave Form |
Pure Sine Wave |
Transfer Time |
0 ms, Between Line mode and Bat mode |
Transfer time: 4ms (typical 2.5ms), line Mode and bypass mode |
Voltage Distortion |
≤6%,Full RCD load |
Voltage Distortion |
≤2%,Full R load |
Overload Capacity |
load≤105%±5%, warning only, 105%+-5%<Load≤125% +-5% ,1min ; 125%±5%<load≤135%±5% , 30S ; Load>135%±5%, 100MS |
Load Peak Ratio |
3:1(max) |
Battery |
Battery Type |
Maintenance free valve regulated lead acid (VRLA) battery |
Battery Voltage |
192VDC |
Battery Capacity |
16*7AH |
External |
16*9AH |
External |
Recharge Time |
7 hours to 90% capacity |
Depended on
battery capacity |
7 hours to 90% capacity |
Depended on
battery capacity |
Charge Current |
1A |
Normal 5Amp. Max 7Amp |
1A |
Normal 5Amp. Max 7Amp |
Display |
LED Mode |
Load level / Battery level / Battery mode / Line mode / Inverter , Bypass ,Over load , Fault |
LCD Mode |
LCD For input output HZ/VAC, Bat %/VDC, Load % and VA/Watts,Temp. Fault Code ,LED for line,bat, Inverter, Bypss,Fault |
Audible Alarm |
Battery Mode |
Beeping every 4 seconds (re-settable) |
Overload |
Beeping every 1 min |
Fault |
Beeping Continuously |
Bettery Low/Charger Fault |
Beeping every 1 min |
Bypass Mode |
Beeping every 2 min |
L/N Inverse |
Beeping every 2 min |
Communications |
RS-232/USB Interface |
With monitoring software |
Working Environment |
Surge protection |
RJ-45 I/O port available for network or Fax/Modem |
Working Temperature |
0ºC~40ºC |
Humidity |
0-95% non-condensing |
Product size |
WxDxH (mm) |
540*260*720 |
260*533*560 |
540*260*720 |
260*533*560 |
Product Weight |
Kg |
85 |
53 |
93 |
55 |
PCS/CTN |
|
1 |
1 |
1 |
1 |
CTN size |
WxDxH (mm) |
730*440*1000 |
360*640*760 |
730*440*1000 |
360*640*760 |
CTN Weight(G/W) |
Kg |
94 |
62 |
102 |
64 |
REMARK |
XG*K-TXB --- Standard Type Internal battery with Transformer, XG*KS-TX---- Long backup Type With Transformer,External battery |