Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
PM60 3PH Rack Module UPS
KEY FEATURES
TECHNICAL SPECIFICATIONS
MODEL | RM120/60X30U-RYY | RM180/60X30U-RYY | RM240/60X-RYY | RM300/60X-RYY | RM480/60X42U-RYY | RM600/60X42U-RYY |
PHASE | 3-phase in/3-phase out | |||||
CABINET CAPACITY* | 120KW | 180KW | 240KW | 300KW | 480KW | 600KW |
BATTERY TYPE | External Battery | |||||
One Power Module Capacity | 60KVA/60KW | |||||
Max. Power Module No. | 2 | 3 | 4 | 5 | 8 | 10 |
INPUT | ||||||
Nominal Voltage | 380VAC/400VAC/415VAC (3Ph+N) | |||||
Voltage Range | 305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load | |||||
Nominal Frequency | 50/60Hz (Auto sensing) | |||||
Frequency Range | 40Hz ~70Hz | |||||
Power Factor | > 0.99 at 100% load, >0.98 at 50% load | |||||
Harmonic Distortion (THDi) | < 3% @ 100% load | |||||
OUTPUT | ||||||
Nominal Voltage | 380VAC/400VAC/415VAC (3Ph+N) | |||||
Voltage Regulation (Steady State) | <=± 1% Typical (balanced load) <=± 2% Typical (unbalanced load) |
|||||
Nominal Frequency | 50/60Hz | |||||
Frequency Range (Synchronized Range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||||
Overload Capability | 110% for 1 hour, 125% for 10 mins , 150% for 1 min and 200ms for >150% | |||||
Harmonic Distortion | <= 2% THD (Linear Load) <= 4% THD (Non-linear Load) |
|||||
Efficiency | Up to 96% | |||||
BATTERY / CHARGER | ||||||
Nominal Voltage | +/- 192V~+/- 240V (Selectable) | |||||
Maximum Voltage | +/- 240V (12V x 40 Pcs) | |||||
Minimum Voltage | +/- 192V (12V x 32 Pcs) | |||||
Floating Charge Voltage | 2.28V/Cell (2.25~2.33 Selectable) | |||||
Boost Charging Voltage | 2.35V/Cell | |||||
Temperature Compensation | Yes | |||||
Maximum Charging Current (Per Power Module) | 18A | |||||
PHYSICAL | ||||||
Cabinet Dimension (D x W x H) mm |
1100 x 600 x 1475 | 1100 x 600 x 2010 | 1065 x 1000 x 2000 | |||
Net Weight (kgs) | 308 | 352 | 516 | 516 | 932 | 1020 |
ENVIRONMENT | ||||||
Operation Temperature | 0 ~ 40ºC | |||||
Relative Humidity | 0 ~ 95% non-condensing | |||||
Altitude* | <1000m for Nominal power | |||||
IP Class | IP 20 | |||||
MANAGEMENT | ||||||
RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC | |||||
Optional SNMP | Power management from SNMP manager and web browser | |||||
STANDARDS | ||||||
Safety | IEC/EN 60950-1; IEC/EN 62040-1 | |||||
EMC | IEC/EN 62040-2 Category C3 |
*If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.
Model | Description | Dimension DxWxH(mm) | Weight (kg) | ||
PM-60 | 3P/3P 60KVA60KW power module | 750 x 438 x 133 (3U) | 44 |